HVAC-Talk: Heating, Air & Refrigeration Discussion banner
21 - 34 of 34 Posts
But From now on I could'nt care what you do. You only have to tell me once.
The rules did not change. It wasn't DIY, we as MODS know how things may be handled differently in different forums.

There is so much behind the scene stuff that members don't know about it would make your head spin.

A good example of that would be the Educational Forums!
 
Not trying to give you a hard time

The rules did not change. It wasn't DIY, we as MODS know how things may be handled differently in different forums.

There is so much behind the scene stuff that members don't know about it would make your head spin.

A good example of that would be the Educational Forums!
But shouldnt this be discussed in pro section. I have seen DIY work on commercial and they have no borders.
 
But shouldnt this be discussed in pro section. I have seen DIY work on commercial and they have no borders.
When the guys that hang here on a regular basis see something that may be suspicious they report the post and the Mod Squad rolls in a takes care of business.


The site administrators had specific reasons for not locking down this forum in the Pro section.

They are comfortable with it they way it is and it's usually not an issue.
 
Discussion starter · #33 ·
not diy

hey guys thanks for your replys ok where do i start,
compressor was wrong type rated at 25 kw for r404a
long pipe run anly allowed to vac out for an hour,
over charged by 10 kg of refrigerant,
no dryer changed
changed dryer vacuumed out to 500 microns charged to 7 k super heat all working fine
 
Thanks for the update.
 