:deadhorse:I have a package unit with electric heat, I put on a new digital t-stat, sometimes it heats then not, fan then not 24v, heat 480 3 ph. went thru 2 stats. Transformer in heat conpartment along with tstat wires anyone have this problem .Im thinking electrical interference from resistence heat.
 
Discussion starter · #3 ·
:deadhorse:I have a package unit with electric heat, I put on a new digital t-stat, sometimes it heats then not, fan then not 24v, heat 480 3 ph. went thru 2 stats. Transformer in heat conpartment along with tstat wires anyone have this problem .Im thinking electrical interference from resistence heat.
30YR OLD YORK 5 TON, Invensys 9725i2 stat
 
Did you try running the unit @ the unit with no stat ? It's not a heat pump right ? Does the t-stat have staging ? Yes i see it has 3H & 2C .
 
Discussion starter · #10 ·
Unit is on our guard house roof no ladder .Only electric heat we have never seen this problem before, Put new sequencers in,always have had an issue.
 
Discussion starter · #16 ·
this is a 2 stage heat ;2 stage cool, with stat off heater works well as suppose to , with face of stat on unit works well with all phaeses heat,blower etc, cycles well, then in about 12 or so ,more or less ,light for heat is onwith no heat no fan.jumper out subbase and everything is fine,next time fan light on heat light on ,i have neither fan nor heat, jumper R-W1 again everything fine to this day ,even put new invensys stat on , does same ,very strange thing.
 