I am trying to figure out what is wrong with a 15 year old York YT centrifugal chiller, 525 ton capacity. The chiller is designed for a 5 deg. delta t on evap side. Here are the conditions that I think are relevant : Evaporator entering water temp:55, leaving water temp:55, condenser entering water temp: 69.5, leaving temp: 71, Suction pressure 8 PSIA, discharge pressure 25 PSIA, Saturated suction and discharge temps were reading correct according to the P/T chart (I can't remember the exact temps though. These readings were taken just before the chiller shut down on a probe error, after running for 10 minutes. It was surging the whole time it was running. The chiller has both freq drive and guide vanes, but both were at 100%.
I have checked and cleaned the cooling tower, inlet strainer, and punched the tubes. The tubes looked clean, but I brushed them anyway. I don't think this is a water flow issue, since I am not getting any temp drop across either barrel. If the water was not moving fast enough, I would expect to see a big delta t.
Luckily it is the end of the cooling season in South Carolina, so I don't need two chillers. I am able to shut this one down and figure it out.
If anyone has a direction to point me in, please advise.
I have checked and cleaned the cooling tower, inlet strainer, and punched the tubes. The tubes looked clean, but I brushed them anyway. I don't think this is a water flow issue, since I am not getting any temp drop across either barrel. If the water was not moving fast enough, I would expect to see a big delta t.
Luckily it is the end of the cooling season in South Carolina, so I don't need two chillers. I am able to shut this one down and figure it out.
If anyone has a direction to point me in, please advise.