I am experiencing very high humidity in my building.
system description:
Two-pipe system with fan coils in each room.
60 ton chiller (Carrier GTN-060; four capacity steps)
about 65 FCU various sizes 7500-12000 BTU
Carrier 42V FCU with electronic thermostat and manual outside air damper.
Chilled water temps at the FCU read between 44 and 52; Chiller setpoint at 45.
Reverse return piping
no circuit setters on the FCUs
all main loop water circulates through chiller during cooling mode.
humidity levels at 70%, mold on some FCU registers.
most FCUs set at 66-70 for dehumidifying.
FCUs don't seem to run long enough to remove humidity when setpoints at at 72-74
outside air dampers set to minimum.
Chiller runs on 1st stage (28%) most of the day when outdoor temps are 90.
When temps reached 100 chiller was on stage 2 (43%)
Location is Northern Virginia.
Any thoughts on causes and what to focus on?
I am the facility manager for the building, HVAC maintenance personnel have looked this over but no firm course of action at this time
Dave
system description:
Two-pipe system with fan coils in each room.
60 ton chiller (Carrier GTN-060; four capacity steps)
about 65 FCU various sizes 7500-12000 BTU
Carrier 42V FCU with electronic thermostat and manual outside air damper.
Chilled water temps at the FCU read between 44 and 52; Chiller setpoint at 45.
Reverse return piping
no circuit setters on the FCUs
all main loop water circulates through chiller during cooling mode.
humidity levels at 70%, mold on some FCU registers.
most FCUs set at 66-70 for dehumidifying.
FCUs don't seem to run long enough to remove humidity when setpoints at at 72-74
outside air dampers set to minimum.
Chiller runs on 1st stage (28%) most of the day when outdoor temps are 90.
When temps reached 100 chiller was on stage 2 (43%)
Location is Northern Virginia.
Any thoughts on causes and what to focus on?
I am the facility manager for the building, HVAC maintenance personnel have looked this over but no firm course of action at this time
Dave