I have a Medium temp rack with two Satellite compressors piped to one suction header that is seperate from the other comprressors. The #2 Sat compressor (wich is the bigger one) will only run for 1-2 minutes and stay off for less than a minute before cycling on again. They are controlled by an Altec controler and is set up to keep suction pressures between 29-36 psi running R22. As soon as the #2 compr kicks on, the "cut-out" light comes on and following a short delay the compressor will shut off, then the "cut-in" light comes on. There are 4 circuits on on this header. Two @ +15 evap and two @ +10 evap. Total Reqired BTU is 103,680. The two compressors are pumping 127,000 BTU at +10° Evap @ 120° condensing. Could having that much excess be causing the short cycling? What should the CI & CO be set at to keep +10 evap with R22? Keep in mind it will over shoot in both directions because of the delay.
Thanks for you thoughts guys.
Thanks for you thoughts guys.