shallowluv

· Professional Member
Joined
·
715 Posts
Discussion starter · #1 ·
Master Bilt- model# tuf 27-no serial info- 404a ref. Compressor info(from comp on top of unit, model# -kajb-007e-1aa-800, serial# -07c612o8r-. Compressor# on tag on back of box-kaab-007e-caa. I went with info on compressor. FLA=10, set cpr valve at 10.1 amps. txv body freezing and suction pressure running 5 psig, so we( my boss man actually ), suspected bad txv. Removed old filter drier and installed new drier. When I went to unsolder the txv oil sprayed out and hit me in the face and caught on fire, when I unsolderd the equalizer tube and distrubution tubes from the txv they both sprayed a little oil and caught on fire. Oil was dripping from the distrubution head assembly so i blew nitrogen through the system, and oil came out with the nitrogen. brazed in new txv, leak tested at 200 psi, no leaks, pulled 250 micron vacum and started system. System still running 5 psig after 15 minutes run time, indoor fan on after coil cooled down, condenser fan running and pulling good airflow,(both coils clean compressor amps 10.1. Ambient=80 degrees, head pressure 265 which= 110 degree condensing temp. fans drawing normal amps and voltage checked out correct. (118 volts) Restaurant closed before I could take superheat and sub cooling. Will an oil logged evaporator cause a low suction? no pump down solenoid. Scratching my head on this one. thanks ahead for any insight, will go back tomorrow for s.h. and s.c. readings. :anyone:
 
assume you are dealing with a weighed in charge. did original txv have a strainer installed ahead of it? with new txv, would rule out this issue. Do you have a tap ahead of the cpr to see what the cprs inlet pressure is?


r404a
 
shallow

Here's a FYI on the compressor differences.

The existing KAJB-007E-IAA-800 is a low temp 502/404A, 218 CFH

The original KAAB-007E-CAA is a low temp 502/404A, 255 CFH

So when the compressor was changed and the original wan't used, probably due to availability, 15% refrigeration capacity was lost.:eek2:

Just thought I'd add to your problems.
 
shallow

Here's a FYI on the compressor differences.

The existing KAJB-007E-IAA-800 is a low temp 502/404A, 218 CFH

The original KAAB-007E-CAA is a low temp 502/404A, 255 CFH

So when the compressor was changed and the original wan't used, probably due to availability, 15% refrigeration capacity was lost.:eek2:

Just thought I'd add to your problems.
The Hershey's branch I have done work for towards richmond is bad about sending the wrong compressors , that and the condensers on the chests are a pita to get clean good because of the way they are made the ones I have serviced run about 5-10 suction right at 95-100 degree condensing and above 80 ambient they don,t work near as good its almost like they are all undersized .
 