Greetings! Has anyone had any problems with Motor Current faults with this particular condensing unit-YCUZ880E8? Been fighting this one for a while. Compressor 1 occasionally faults on Motor Current. Problem: ISN reads low motor current but an amp meter indicates approx 2/3 RLA. Also, sometimes the contactors will not energize at startup. I'm thinking either a wiring issue or main processing board. I've gone over all wiring connections several times. CT has been changed as well as relay board no.1. MP and HP switch are not the culprits. I hate being a parts changer so any fresh ideas would be much appreciated. Cheers! Dean.