HVAC-Talk: Heating, Air & Refrigeration Discussion banner
21 - 30 of 30 Posts
Read your technical instructions, some controllers want a 24v AC power supply that's bonded and some don't want it bonded.

DO NOT MIX the two.

I know from experience if you bond a power supply for a jace edge that doesn't want it you will blow up the jace and your laptop.
 
Sam.

It has nothing to do with routine and more to do about reliability and ability to troubleshoot. Again, there are the cases where it's correct to float the transformer.
 
Save
Sam.

It has nothing to do with routine and more to do about reliability and ability to troubleshoot. Again, there are the cases where it's correct to float the transformer.
Good day control$,

I appear to be unable to explain my point... it has nothing to do with reliability and troubleshooting ... nor is it more or less correct to ground or to isolated the 24VAC power supply. Can you not grasp this? Read what MaxBurn just posted, as perhaps you can better understand what he posted.

That said, do as you see fit, as I give up... I was simply trying to present reasons why one should not "always" do something without understanding the why.

Cheers,

Sam
 
Sam.

I respect your knowledge so I'm trying to understand your position. No harm done since your not working on my equipment. My secondary's are grounded.
 
Save
Can you elaborate on this? I know that Johnson has isolated comms, and IO, so they don't really care whether your 24v power is good bad grounded, whatever.... but what bad things happens when you ground it?
I asked about this. And this seems like a good answer:

my controllers are within panels that have mixed voltages present (i.e. class 1 and class 2). Since my low voltage/class 2 controllers are isolated there is much less chance of having a safety/shock hazard if someone mistakenly ... or a rouge wire goes awry... connects/touches a class 1 voltage to my controller or its inputs. If my controller was connected or referenced directly to ground, it would be a very bad day for both the equipment and anyone present.
Also the bit about lightening strikes.

Since the JCI stuff is made to be isolated, it can survive without a ground, unlike Alerton and others.grounding is a MUST on those, but not a must universally.

Add to that various unusual but possibly significant issues that can arise. I really like the isolated setup. Not only does it seem more robust and reliable, it can easily confuse the less savvy so I can get a foot into the building. I will still ground every Alerton, Distech, and ALC system I meet. But it is good to have an eye out for other systems that do not need it.

Very interesting conversation.
 
I asked about this. And this seems like a good answer:

Also the bit about lightening strikes.

Since the JCI stuff is made to be isolated, it can survive without a ground, unlike Alerton and others.grounding is a MUST on those, but not a must universally.

Add to that various unusual but possibly significant issues that can arise. I really like the isolated setup. Not only does it seem more robust and reliable, it can easily confuse the less savvy so I can get a foot into the building. I will still ground every Alerton, Distech, and ALC system I meet. But it is good to have an eye out for other systems that do not need it.

Very interesting conversation.
Good day numbawunfela,

As mentioned, there is no "right" or "wrong" way of powering gear...there are pros and cons to both approaches in terms of having a power supply input grounded or isolated. In my case, I have never had a specific need and felt that the benefits car out weighed the negatives of having an isolated power input. I have being using this approach for over 30 years in all of my designs and I still have some of these old devices in the field... and are still working. One in particular is part of an commercial tower's freight elevator and has been running 24/7 since 1996 with zero failures... not even a reboot has been required. So, any reliability concerns are out the window. That said, there are systems out there with a ground referenced power supply and these can work a long time too. It all depends upon the application, etc.

Relying on a common ground can be very problematic, as people assume that the ground potential is the same everywhere... this is not the case and can vary under a variety of conditions where a Lightning strike, as I mentioned, is the most common. However, even local changes can occur from a static discharge. It is much harder to control the current/energy flow from a static zap in a ground referenced device. If one does not "control" or direct the static zap's current, then the device (and/or downstream connected devices) can become damaged or cause them to reboot/restart. Isolated powered devices are not immune from this issue, but it is a bit easier to control the static zap energy to a location that has a dedicated or isolated ground point... now the static discharge bypasses the internal components (hopefully) and so minimizes damage or a triggered reboot ... this is all part of EMC compatibility and/or approvals that may be required for the devices.

The other issue that can occur is differential ground currents. Remember that if there is a voltage differential between two points, a current will flow. So... if the "ground" at one place is different than the "ground" at another, then you will get a differential current and these currents can be significant. This is why the RS485 interfaces typically have a 100 ohm or so resistor between the "ref" terminal and the device's local reference "ground". If not, then a differential current can occur and create all sorts of issues including a potential safety hazard.

Anyway... there is a lot to all of this and my intent was to remind others to be mindful of these details and understand the "why" things are done... and not simply do things because it was done before, or because this is required for some Manufacturers, etc. Failing to understand the why can be lead to all sorts of issues.

Cheers,

Sam
 
I asked about this. And this seems like a good answer:



Also the bit about lightening strikes.

Since the JCI stuff is made to be isolated, it can survive without a ground, unlike Alerton and others.grounding is a MUST on those, but not a must universally.

Add to that various unusual but possibly significant issues that can arise. I really like the isolated setup. Not only does it seem more robust and reliable, it can easily confuse the less savvy so I can get a foot into the building. I will still ground every Alerton, Distech, and ALC system I meet. But it is good to have an eye out for other systems that do not need it.

Very interesting conversation.
We install JCI products mostly and have done Spyders in the past which unlike JCI recommend to be grounded.
 
Save
Awesome as usual, Sam. I didn't know that there is often an internal 100 Ohm resistor between the RS485 interface and a controllers 24v reference.

Makes sense. The documentation I seen often shows grounding an RS485 ref terminal through a 100 Ohm resistor.... I usually use a 120 as I have them lying around as a termination resistor.

Very interesting.
 
Awesome as usual, Sam. I didn't know that there is often an internal 100 Ohm resistor between the RS485 interface and a controllers 24v reference.

Makes sense. The documentation I seen often shows grounding an RS485 ref terminal through a 100 Ohm resistor.... I usually use a 120 as I have them lying around as a termination resistor.

Very interesting.

Good day numbawunfela,

Your comment of "I didn't know that there is often an internal 100 Ohm resistor between the RS485 interface and a controllers 24v reference." is incorrect. The 100 ohm series resistor is typically placed between the RS485's "ref" terminal and the reference "ground" used by the RS485's transceiver (which you correctly stated). The RS485's transceiver "could" be the same one of the equipment's input power supply, but one cannot make this assumption. You will note that I used the term "local reference" ground in my original comment. This specific detail was on purpose as there is the potential of misunderstanding the term "ground", as "ground" means different things depending upon the context. Ground could mean... Earth Ground... or a common voltage reference voltage that other voltages are referenced to.

On a side note, this "ref" terminal series resistor is meant to limit or minimize differential currents that can exist between interconnected RS485 device. The voltage across it should be small... and if not, then you have large differential currents which could create misinterpretation of the electrical levels as seen by the RS485 transceiver.

Cheers,

Sam
 
21 - 30 of 30 Posts
You have insufficient privileges to reply here.