Looks like this happened June 28,2021 and you were at 14.0.1 CCT has been updated since then.
Looks like a custom program? Can you elaborate?
This happened to one of my techs when he was attending a virtual CCT class. He added some side loops and VFD drives and tried to make some connections but the connections didn't work and created this issue. Not sure why but once I deleted one of the side loops it worked.
Can you send me the caf file so I can look at it?
 
Save
Had the same issue with v14.0.1, upgrade to v14.0.2.2 (the latest release). Also helps to start CCT as "Run as Administrator".

A work around in v14.0.1 is to test in Release Mode 10.4. Save the program to a different name like XXXX_test.caf then change to v10.4, open program upgrade & test. No need to select a controller to test. Kinda of a pain to switch back and forth to resolve issues but it worked for me.
 