I have a Fujitsu outdoor unit AOU36RML, 2 indoor units ASU9RMLQ and 1 ASU18RMLQ. When the temp setting in the room reaches or exceeds the set point the indoor unit will slow down to very low fan speed. No warm air comes from the unit. Which I believe is normal. But the outdoor unit continues to run forever or until I turn it off with the remote. Very rarely will the outdoor unit turn off.
Also twice this year I woke the a 64 degree house when the unit was set to 68. Both times the outdoor unit was not running. I turned off the system with the remote. Waited a few minutes turned it back on. The outside unit kicked on and a few minutes later I had heat.
Also what you set the temp at with the remote and the temp of the room are two different things. You set the remote to 68 and the indoor unit will not shut down until the room is about 70-71.
Sunday and part of today the system appeared to working right. Temp was set at 68. The outdoor unit and indoor unit were running and producing heat and keeping temp as set. I think the system is working right if the outdoor unit runs continually as long as the indoor unit puts out heat and keeps the temp constant. I am right or wrong? But this evening the outdoor unit was again constantly running and no heat from the indoor units. The temp was set at 68. It got down to 66 in the house. I turned off the system waited a few minutes turned it back and got heat. I am to the point I have to run it manually.
Again this is in heat mode. When in cool mode what you set the remote at is what the temp in the room remains. The outside unit cycles on and off which appears normal to me.
What do you think is wrong with it. The system was installed in 2009 or 2010. I am at my wits end because I can't get anyone to service it in my area. The contractor who installed it won't return my calls. Any input would be gratefully appreciated.
Also twice this year I woke the a 64 degree house when the unit was set to 68. Both times the outdoor unit was not running. I turned off the system with the remote. Waited a few minutes turned it back on. The outside unit kicked on and a few minutes later I had heat.
Also what you set the temp at with the remote and the temp of the room are two different things. You set the remote to 68 and the indoor unit will not shut down until the room is about 70-71.
Sunday and part of today the system appeared to working right. Temp was set at 68. The outdoor unit and indoor unit were running and producing heat and keeping temp as set. I think the system is working right if the outdoor unit runs continually as long as the indoor unit puts out heat and keeps the temp constant. I am right or wrong? But this evening the outdoor unit was again constantly running and no heat from the indoor units. The temp was set at 68. It got down to 66 in the house. I turned off the system waited a few minutes turned it back and got heat. I am to the point I have to run it manually.
Again this is in heat mode. When in cool mode what you set the remote at is what the temp in the room remains. The outside unit cycles on and off which appears normal to me.
What do you think is wrong with it. The system was installed in 2009 or 2010. I am at my wits end because I can't get anyone to service it in my area. The contractor who installed it won't return my calls. Any input would be gratefully appreciated.