Hi, and thanks for the opportunity to discuss my problem. I apologize for the length of this but I want to be thorough. I am familiar with HVAC equipment having assisted my Uncle (a mechanic) during summers out of school (but this was back in the 70’s) so beyond the basics of the systems I'm at a loss for experience and insight.
I have recently had my hydronic boiler and potable water heater systems updated/upgraded from oil to NG. The unit is now about 6 months old.
This is a Thermo-Dynamics Boiler, CWL-GS series with a potable water heat exchanger installed (eliminating the old, stand alone, 40 gal tank). The system was also installed with TACO electronic zone valves, for a single, whole-house zone, to keep hot water from gravity feeding to the cast iron radiators throughout the house when only potable water is called for (many years ago this 110 year old house was heated with steam). Low limit is set at 145 degree and high limit set at 165 degree with a 10 degree differential. The boiler control is a Beckett AquaSmart 7600, programmed with a 20 minute override/delay when potable hot water is called for.
The hydronic system consists of several cast iron radiators: 6 each, 24 x 40 inch, 4 each 24 x 60 inch, and one modern Runtal 22 x 48 Omni Panel. Return and supply piping in the basement looks to be at least 2 inch iron at about 150 linear feet, with 1.25 inch risers to the radiators at about 180 linear feet. I was estimating that the total water volume of the system was about 125 gal.
As the very cold weather set in a few weeks ago, we started experiencing some pretty severe water hammering that was heard throughout the whole house. The water hammering occurs after the system starts after it has been off for several hours (primarily when thermostat programmed for “away”) and has cooled, except for the main chamber. I bled excess air from the system (air was normally only present in one large radiator on top floor, though I did check every other one, a total of 10). This seemed to eliminate the hammer for the next 24 hours or so… but when I went into the basement the floor was covered with water purged through the pressure relief valve on the boiler.
I examined the unit more closely and found that the TACO air scoop (fitted with a air escape valve on top and a Honeywell TK300-30-1, 4.4 gal capacity expansion tank below) was installed backwards and did not have the required 18-inch horizontal run leading to the scoop. The scoop was also installed out of spec as the circulator pump was installed preceding the scoop (about a 10 inch rise into an 90-elbow then 5 inches of horizontal run, all 1.25 inch copper). Additionally, mechanical temperature/pressure combo gauge and the heat exchanger were both found to be defective (boiler water was leaking past a bad weld on the outlet fitting). After a few more start-ups I am reasonably certain that the hammer occurs when the zone valve on the return side opens (the supply side seems to open a moment earlier because - I think - the supply side pipes heat up and cause the actuator to open a little sooner than the colder return side).
I contacted my mechanic and he replaced the heat exchanger (under warranty) and replaced the TACO air scoop with a Watts air scoop (in proper direction). No other piping modifications were made. The only difference in the installation from the Watts specs is that the circulator pump precedes the air scoop, pumping water from the boiler, past the air scoop and to the radiators (rather than pulling from the radiators and into the boiler, then into the air scoop). *The Watts unit does not specify any specific horizontal run leading to the scoop.
My installation mechanic refilled the system while I bled the radiators. Using the newly installed gauge, he checked the pressure relief valve that opened correctly at 30#. He checked the boiler fill valve that closed correctly at 15#. The potable water heat exchanger no longer leaked. The unit was fired up and the low and high limits were tested and functional. The circulator operated as expected and the zone valves opened to allow circulation. I considered the job done at that point.
**The following morning when the thermostat called for heat (after overnight thermostat “away” mode) the water hammer returned. I inspected the unit and found about 2 gal of water had released from the pressure relief valve (I knew this was the source because I had a small pan under the pipe).
Q. Air entering my system is my core problem?
Q. So what do I need to do to eliminate this water hammer and pressure valve release problem?
Q. Is there a hydronic shock absorber that could or should be installed to stop or reduce the hammer.
Q. Is the 4.4 gal expansion tank properly matched for the size of the system?
Q. Is there harm to installing a larger, or second, expansion tank?
Q. Is the air I continue to purge from the highest radiators in the house entering the system through the pressure relief valve when it opens?
Q. I’m not sure my mechanic has any more suggestions… What is my next step?
I have recently had my hydronic boiler and potable water heater systems updated/upgraded from oil to NG. The unit is now about 6 months old.
This is a Thermo-Dynamics Boiler, CWL-GS series with a potable water heat exchanger installed (eliminating the old, stand alone, 40 gal tank). The system was also installed with TACO electronic zone valves, for a single, whole-house zone, to keep hot water from gravity feeding to the cast iron radiators throughout the house when only potable water is called for (many years ago this 110 year old house was heated with steam). Low limit is set at 145 degree and high limit set at 165 degree with a 10 degree differential. The boiler control is a Beckett AquaSmart 7600, programmed with a 20 minute override/delay when potable hot water is called for.
The hydronic system consists of several cast iron radiators: 6 each, 24 x 40 inch, 4 each 24 x 60 inch, and one modern Runtal 22 x 48 Omni Panel. Return and supply piping in the basement looks to be at least 2 inch iron at about 150 linear feet, with 1.25 inch risers to the radiators at about 180 linear feet. I was estimating that the total water volume of the system was about 125 gal.
As the very cold weather set in a few weeks ago, we started experiencing some pretty severe water hammering that was heard throughout the whole house. The water hammering occurs after the system starts after it has been off for several hours (primarily when thermostat programmed for “away”) and has cooled, except for the main chamber. I bled excess air from the system (air was normally only present in one large radiator on top floor, though I did check every other one, a total of 10). This seemed to eliminate the hammer for the next 24 hours or so… but when I went into the basement the floor was covered with water purged through the pressure relief valve on the boiler.
I examined the unit more closely and found that the TACO air scoop (fitted with a air escape valve on top and a Honeywell TK300-30-1, 4.4 gal capacity expansion tank below) was installed backwards and did not have the required 18-inch horizontal run leading to the scoop. The scoop was also installed out of spec as the circulator pump was installed preceding the scoop (about a 10 inch rise into an 90-elbow then 5 inches of horizontal run, all 1.25 inch copper). Additionally, mechanical temperature/pressure combo gauge and the heat exchanger were both found to be defective (boiler water was leaking past a bad weld on the outlet fitting). After a few more start-ups I am reasonably certain that the hammer occurs when the zone valve on the return side opens (the supply side seems to open a moment earlier because - I think - the supply side pipes heat up and cause the actuator to open a little sooner than the colder return side).
I contacted my mechanic and he replaced the heat exchanger (under warranty) and replaced the TACO air scoop with a Watts air scoop (in proper direction). No other piping modifications were made. The only difference in the installation from the Watts specs is that the circulator pump precedes the air scoop, pumping water from the boiler, past the air scoop and to the radiators (rather than pulling from the radiators and into the boiler, then into the air scoop). *The Watts unit does not specify any specific horizontal run leading to the scoop.
My installation mechanic refilled the system while I bled the radiators. Using the newly installed gauge, he checked the pressure relief valve that opened correctly at 30#. He checked the boiler fill valve that closed correctly at 15#. The potable water heat exchanger no longer leaked. The unit was fired up and the low and high limits were tested and functional. The circulator operated as expected and the zone valves opened to allow circulation. I considered the job done at that point.
**The following morning when the thermostat called for heat (after overnight thermostat “away” mode) the water hammer returned. I inspected the unit and found about 2 gal of water had released from the pressure relief valve (I knew this was the source because I had a small pan under the pipe).
Q. Air entering my system is my core problem?
Q. So what do I need to do to eliminate this water hammer and pressure valve release problem?
Q. Is there a hydronic shock absorber that could or should be installed to stop or reduce the hammer.
Q. Is the 4.4 gal expansion tank properly matched for the size of the system?
Q. Is there harm to installing a larger, or second, expansion tank?
Q. Is the air I continue to purge from the highest radiators in the house entering the system through the pressure relief valve when it opens?
Q. I’m not sure my mechanic has any more suggestions… What is my next step?