HVAC-Talk: Heating, Air & Refrigeration Discussion banner
21 - 40 of 52 Posts
Discussion starter · #21 ·
M#twe120e300ab let me see if I can post a vid we are gonna clean it Monday but this unit has been running for a little less than a year I dont see how it could just now be factory oil
 
I have several TTA120B's at one school. Side return, had to put a cookie sheet in them even though the coils were cleaned thoroughly. Didn't drip all the time, but often enough that it became a nuisance.

Our sheet metal shop made up some .067 aluminum cookie sheets and haven't had any repeat problems in 14 years.
 
Save
M#twe120e300ab let me see if I can post a vid we are gonna clean it Monday but this unit has been running for a little less than a year I dont see how it could just now be factory oil
Cleaning may cure it, but it could also be due to leaks in the coil. Oil from the system contaminates the fins and the water falls off. A quick scan with an electronic leak detector might save you some trouble. If you don't pick up anything then so be it, wash the coil and see what happens.
 
I am having this exact same issue on a Trane TWE150 vertical that we installed last week. Water drips off the return side of the evap and doesn't reach the drain pan. Coil was rotated 4 degrees. It might be worth looking at the staging of the evap again as explained by gravity but if this was something that affected condensate management, shouldn't Trane have wrote something about it in the install manual? I turned in the drive sheave from 6 turns out to 3 turns out thinking that increased air velocity would keep the water on the coil longer and allow it to run down to the drain. This didn't help. When you figure it out, let us know. I'll do the same.
 
Discussion starter · #25 ·
Gonna give it a good cleaning tomorrow but I doubt it is residual oil being it has been running for almost a year. If all else fails I'll install the "drip eliminator" untill I can figure it out.
 
I have had this same issue with Trane commercial air handlers. As stated clean the coil with a detergent base cleaner like triple D. I have also installed a fan off time delay to run the blower 3-5 minutes after cooling shuts off to help dry the condensate from coil
 
Discussion starter · #27 ·
I stand corrected. Holy crap its like a night and day difference. A quick spray down with cal-spray no rinse and brush the coil down with a soft bristle brush and not one damn drop off the coil now even when it shuts down. Thank you guys very much for the info. Boss man still wants drip kit installed so I'll post pics of what that looks like when its done should be here around 1030 this morning. Thanks again guys!
 
Doesn't look like any drip eliminator I've ever seen. I'm not understand how a louvered grille would prevent dripping. Am I missing something here? Something not seen in the picture?

Does changing the direction of the air right before the coil prevent drips?

It will add a bit of pressure drop to the return though.
 
Discussion starter · #30 ·
Nope thats what they shipped marked ah drip kit and installed as per instructions. Cleaning the coil worked like a charm though I'm not to worried about that stupid thing
 
Discussion starter · #35 ·
Ok we are back to square one. That same twe120 has water dripping off the coil again and the drip elimimator is garbage!! Now to add insult to injury the same place has 2 more twe90's both doing the same thing
 
Well.... If it's clean and it drips.............try a coat of good ol WD40 to see if it sheets down correctly again. As long as the detergent was on the coil the water could not develop surface tension that would let it bead. I'm not sure but a good old oily coil might not either. I've seen a lot of nasty coils that never drip, just the clean ones.

Just my observations and I'm not in favor of nasty coils.
 
Save
Have you checked your air flow? Whats the TESP of the unit? Check that against the fan curve and see what you are moving.
If your In a humid area and moving lower then the required air then you will have excess water being built up on the coils.
Any way of checking the FPM on the unit? Id confirm thats not out side the high end of the manufactures limit.

It seems like you have checked everything on the refer side and also cleaned the coil so you know ( Or hope ) their Isn't any oil left on it. Now I think you need to work on the air side of things to confirm your within spec.
 
Discussion starter · #39 ·
Ok I'm trying to make time to get back over there we've been crazy busy. I'm gonna take the airflow hood and see about getting a monometer. We are having trouble locating the prints for this job and the estimator for this job quite a couple weeks before this problem
 
Should be able to get most of your flow data from the AHU IOM. Far as the duct work may just be best to proportion at this point. Either way may need a larger return or a sheeve change.
 
21 - 40 of 52 Posts
You have insufficient privileges to reply here.