Don't rule out the cooler tubes also!
As a side note,I wouldn't put too much faith in the D Tek leak detector, they've failed me and other mechanics more than once. I highly recommend the H-10G ( I think made by Bacharach now) leak detector,especially for 134a. Calibrate it, and put in the "small" leak setting (for 134a always) its way more accurate, in my opinion. 400 bucks, but worth every penny!
Anyway, you've ruled out all external joints, including all relief valves, guide vane shaft seal (behind the black plastic chain guard), and motor lead terminals ?
Next, if you want to pick the condenser first, I'd secure water valves, drain tube bundle, and drop heads on BOTH sides, and remove the division plate. Next, with some compressed air or Nitrogen, I'd blow out the tubes of water real good, possibly a few times until they're pretty dry, no excess water. Next purchase #2 rubber stoppers, and "cork" lightly both ends of the tubes. Come in the next day, see if any popped out. If not, sniff one by one, each and every tube and see if your leak detector goes off. The leakers, if any, will have to be faced to the end (tube) sheet, and plugged with brass plugs on both sides, and re-leak checked. If no luck with the condenser, then repeat with the cooler tubes. Also, I'd spray alot of bubble solution (such as Big Blue) on the tube sheet, and see if any bubbling appears around the tubes and the sheet, maybe there is a bad tube roll. Lots of fun!!!
Ok a couple of more things: High approach, do you have the right cooler and condenser water pressure drops?
Also, the right charge is critical in these machines, especially for part load oil reclaming. Make sure your suction temp is design at full load, according to the ARI performance design specs. ( as well as those water flows). Also, at part load, when the guide vane position is at 3% or less, you should see the vertical sightglass on the oil reclaim showing a foamy flow of refrigerant and oil mix, not a full glass, but spurts. If its full, remove some refrigerant, if its empty, start adding until you see it, watch, it appears suddenly! Thats the proper way to 'trim" a charge on an 19XR/XRV. Also, make sure your cooler tubes are clean,just something to think about, some people think their chilled water system is fairly clean, when in fact it is not, and they overlook the possibility of dirty tubes. I've had big cooler approaches on machines, and they weren't low on charge, the cooler tubes were very dirty! Also, these machines are very sensitive to dirty tubes, especially in the condenser. Also, at full load, watch your discharge superheat, make sure its over 100 degrees at least. Lastly, there could be excess oil in the charge. Did you ever have to add oil to the compressor? If the oil isn't reclaiming because of improper charging, it may be "stuck" in the cooler,laying on top of the refrigerant, causing the high approach. Also, check the isolation ball valve that separates the liquid line from the condenser to the cooler, and make sure its fully open! A possibility, but not too common is a stuck linear (coffee can) float, but usually if they stick, they stick real bad, causing the machine to shut down on a low refrigerant alarm. I would check all of this before blaming the tube leak, because it is possible, but not very probable, and that job is the last thing you want to do, when you can just check these things first. One more thing, "zero" out the evap. transducer, it could be out of range, giving you a bad reading. How- to is in the Carrier Start Up, Maint, and Operation manual. (And hopefully the VFD is running right, that a whole 'nother issue in itself. Just figure I'd mention that, but don't worry about that yet.
If you know any of this, I don't mean to insult your intelligence, just putting all the possibilites out there. Good luck! Let us know what you find!
Shop Hound, you're right about XR's. Keep the tubes real clean, cooler tower water the better, and you have a trouble free, very low maintenance machine for years! A little noisy, but worth it! No low pressure air leaks to worry about, or open drive seals to leak! End of the season, clean the cond tubes, leak check, take an oil sample...done! Ready for next season!