Hello group,
May I preface my post in that I am a homeowner and have a question. I use trained (I hope) people, that is, a couple local hvac businesses for any repair/maintenance, as I lack the knowledge and tools to diy. That being said, being a mechanical engineer with a basic knowledge of refrigeration cycles, besides the fact that I just like to UNDERSTAND things, I have a question I wish you to opine upon regarding my own unit so that I will at least have a clue about what said pro is advising. OK....
*American Standard 3 Ton packaged heat pump ~ 7 yrs. old
*Spring "Tune-Up" every 2 years, never needed freon or to even clean the coils, spotless inside.
*Late last summer, cooling seemed to fall off a bit
*Called hvac co..... tech said 'charge just a bit low' and added freon
*I noticed he had the bottle 'upside down' while he added freon and questioned that???? He said that would give it an extra shot of oil??
*I let it slide as the unit seemed back to normal again... then a couple weeks later the evap coil started freezing up pretty regularly as the weather got way more humid.
*Got DIFFERENT tech to come out and he said it was significantly overcharged by last tech... and he recovered freon until charge was back to normal.... but advised that upside down bottle was NOT GOOD as that fills w/ liquid vs. gas.. said watch it and let him know... unit functioned flawless rest of summer and all winter in heat mode.
*NOW... if you're still here, I bet i'm going to get a knowledgeable response
Problem is....
*When selecting cooling mode, unit starts and runs normally... both fans on, compressor on....
*on a moderate evening last nite (~80 deg): normal pressures according to curves supplied with literature..
Suction = 75 psi
Discharge = 220 psi
Outlet temp at nearest vent = ~56-58 deg (is that good for the weather?? I've never measured it before)
*THEN.... the longer the unit runs, the warmer the outlet temp becomes... I mean, It takes like 4-5 hours, and then the outlet temp is ambient. and it does it very gradually.... pretty much linearly with time...
*I've repeated this process over 2-3 days, letting the unit stay off at nite (with the windows open), and restarting the next day, with the SAME results... cools initially.... falls off gradually.... ambient in a few hours...
*Unit runs continuously, no overheat/overcurrent/diff_press trips... NO cycling. Starts easy, no odd noises, runs smooth
*OH. also, at first, when the unit seems to be cooling fairly, the condensor coils are warm, and the drain plumbing is dripping steadily, and the air coming out the top is quite warm (obviously if the coils are warm). As the cooling diminishes, the coils/exhaust air cools as well, and the condensation drip quits.
I called my tech, and he said maybe the resistance strips are energizing. that doesn't make sense to me because of the gradual nature... and the symptoms above.... all the sequencing of the unit seems like it's working properly. I can summon heat... aux heat if i crank up the thermostat, emergency heat... the circ fan delay circuit is working... the heat mode defrost cycle always has worked,.... anyway, dont think my aux heat is energizing while in cooling mode..... think the sequencing board is fine??
I'm wondering if MAYBE???? due to the liquid freon addition the drier/filter has become either saturated?? or clogged?? and kind of works fair, at best, for a while after the unit has sat, then clogs back up.... or also possibly, that the restriction? has reduced the coolant flow such that the unit will work at reduced efficiency for awhile until conditions finally overwhelm it??? IE... the heat balance is compromised in the HEAT direction with the unit in cool???
ANYONE??????
I guess you would REALLY need those pressures when the unit is NOT cooling anymore to help firmly diagnose..... and I don't have gauges... got those readings above from the tech last nite, who said the pressures are normal, run it tonite and let me know what happens.... and he obviously can't hang around for hours waiting for further readings....
Also, I would request info on what to look for with regard to frost on the uninsulated lines... my tech said the filter/drier line would be frozen if it was plugged up, but that doesn't make sense to me??? as it's on the 'hot' (condensor) side of the loop ???
If you've read this so far, I appreciate it and your advice. I respect your trade, and your discrection should you so choose... I'd just like to have a clue when my unit gets ...again.... diagnosed, so I don't get caught blindly replacing perfectly good parts.... AND... I want to understand what happened to it...
Thanks and Regards,
Brian MacKinnon
Guntersville, AL
May I preface my post in that I am a homeowner and have a question. I use trained (I hope) people, that is, a couple local hvac businesses for any repair/maintenance, as I lack the knowledge and tools to diy. That being said, being a mechanical engineer with a basic knowledge of refrigeration cycles, besides the fact that I just like to UNDERSTAND things, I have a question I wish you to opine upon regarding my own unit so that I will at least have a clue about what said pro is advising. OK....
*American Standard 3 Ton packaged heat pump ~ 7 yrs. old
*Spring "Tune-Up" every 2 years, never needed freon or to even clean the coils, spotless inside.
*Late last summer, cooling seemed to fall off a bit
*Called hvac co..... tech said 'charge just a bit low' and added freon
*I noticed he had the bottle 'upside down' while he added freon and questioned that???? He said that would give it an extra shot of oil??
*I let it slide as the unit seemed back to normal again... then a couple weeks later the evap coil started freezing up pretty regularly as the weather got way more humid.
*Got DIFFERENT tech to come out and he said it was significantly overcharged by last tech... and he recovered freon until charge was back to normal.... but advised that upside down bottle was NOT GOOD as that fills w/ liquid vs. gas.. said watch it and let him know... unit functioned flawless rest of summer and all winter in heat mode.
*NOW... if you're still here, I bet i'm going to get a knowledgeable response
Problem is....
*When selecting cooling mode, unit starts and runs normally... both fans on, compressor on....
*on a moderate evening last nite (~80 deg): normal pressures according to curves supplied with literature..
Suction = 75 psi
Discharge = 220 psi
Outlet temp at nearest vent = ~56-58 deg (is that good for the weather?? I've never measured it before)
*THEN.... the longer the unit runs, the warmer the outlet temp becomes... I mean, It takes like 4-5 hours, and then the outlet temp is ambient. and it does it very gradually.... pretty much linearly with time...
*I've repeated this process over 2-3 days, letting the unit stay off at nite (with the windows open), and restarting the next day, with the SAME results... cools initially.... falls off gradually.... ambient in a few hours...
*Unit runs continuously, no overheat/overcurrent/diff_press trips... NO cycling. Starts easy, no odd noises, runs smooth
*OH. also, at first, when the unit seems to be cooling fairly, the condensor coils are warm, and the drain plumbing is dripping steadily, and the air coming out the top is quite warm (obviously if the coils are warm). As the cooling diminishes, the coils/exhaust air cools as well, and the condensation drip quits.
I called my tech, and he said maybe the resistance strips are energizing. that doesn't make sense to me because of the gradual nature... and the symptoms above.... all the sequencing of the unit seems like it's working properly. I can summon heat... aux heat if i crank up the thermostat, emergency heat... the circ fan delay circuit is working... the heat mode defrost cycle always has worked,.... anyway, dont think my aux heat is energizing while in cooling mode..... think the sequencing board is fine??
I'm wondering if MAYBE???? due to the liquid freon addition the drier/filter has become either saturated?? or clogged?? and kind of works fair, at best, for a while after the unit has sat, then clogs back up.... or also possibly, that the restriction? has reduced the coolant flow such that the unit will work at reduced efficiency for awhile until conditions finally overwhelm it??? IE... the heat balance is compromised in the HEAT direction with the unit in cool???
ANYONE??????
I guess you would REALLY need those pressures when the unit is NOT cooling anymore to help firmly diagnose..... and I don't have gauges... got those readings above from the tech last nite, who said the pressures are normal, run it tonite and let me know what happens.... and he obviously can't hang around for hours waiting for further readings....
Also, I would request info on what to look for with regard to frost on the uninsulated lines... my tech said the filter/drier line would be frozen if it was plugged up, but that doesn't make sense to me??? as it's on the 'hot' (condensor) side of the loop ???
If you've read this so far, I appreciate it and your advice. I respect your trade, and your discrection should you so choose... I'd just like to have a clue when my unit gets ...again.... diagnosed, so I don't get caught blindly replacing perfectly good parts.... AND... I want to understand what happened to it...
Thanks and Regards,
Brian MacKinnon
Guntersville, AL