I guess I won't be doing any condenser only change outs on heat pumps. But I've never had that happen on a cooling only system. Usually I don't even need to adjust the charge. Of course I have no way to verify how many BTU's the system produces, but the owners say it cools better and the bill goes down. But I will definitely try to pursuade them into a new system.

Recently a building with (4) 10 SEER systems had all of the condensing units stolen. A contractor came out and replaced all of the units with Goodman 13 SEER units but did not even try to sell them new coils. I thought the building felt really humid when I was there but I was just visiting, not working so I didn't get involved.
 
That is a very poorly put together "simulated" test.

Where do I start, they didn't list model serial numbers, so I took some Trane r-22 13 seer matched system data. The Trane system is rated at 35,800 btus, but at OD of 95°, ID of 80°, and Wet bulb of 71° the system rating drops down to 20,900 BTU.

The tester did not take into consideration the effects of the high OD and ID temp and neglected to measure wet-bulb. They simply took the nameplate data, which is inaccurate. They also didn't measure airflow, if the system is not putting out the rated cfm the output will drop.

Come back with some correctly prepared tests and I'll stop doing change outs.
 