Perhaps I should clarify. The system was installed correctly for 2000 standards and code enforcement. The return didn't need a plenum in 2000 and even with today standards of 2011 (local code) the CFM's don't need to be tested based on the system.
The only thing they check is that the system ducts don't leak beyond a certain percentage. They don't need to prove that a 4 ton unit requiring 1400-1600 CFM's have the proper return or supply.
You have a 2000 Sq foot home and a 4 ton unit, the ducts leak 10%....you're good. System is passed.
Other than the 2000 IMC code that states that return air is required to have 6sq inches of return per 1k btu. So, it wasn't up to the 2000 standard.
A contractor doesn't have to "prove" anything. It's the inspectors job to "find" the problems.
I've never seen an inspector check for leakage %, unless it was a commercial building spec.
Actually, an inspector IS SUPPOSED to make sure that a system has proper return.
Square footage is only one part of tonnage requirement. The state of Ohio, and Kentucky require a load calculation with any new home permit, and most states also require it.
IMC:
"SECTION 312 HEATING AND COOLING LOAD CALCULATIONS
312.1 Load calculations. Heating and cooling system design loads for the purpose of sizing systems, appliances and equipment shall be determined in accordance with the procedures described in the ASHRAE/ACCA Standard 183. Alternatively, design loads shall be determined by an approved equivalent computation procedure, using the design parameters specified in Chapter 3 of the International Energy Conservation Code."
"603.2 Duct sizing. Ducts installed within a single dwelling unit shall be sized in accordance with ACCA Manual D or other approved methods. Ducts installed within all other buildings shall be sized in accordance with the ASHRAE Handbook of Fundamentals or other equivalent computation procedure."
So, yes, they do.